What Happens During an EICR Inspection? Dead Testing vs. Live Testing Explained

If you own, manage or rent out a property in the UK, you have probably heard the term “EICR”. An EICR inspection (Electrical Installation Condition Report) is the standard way to find out whether the fixed electrical wiring in a property is safe, and it is a legal requirement for most rented homes in England.

Many landlords and homeowners book one without knowing what the electrician will actually do. Where do they look? Why is the power switched off for part of the visit? What do “dead testing” and “live testing” mean?

At London Property Inspections, we explain this to clients every day. Here is what happens, step by step.

What Is an EICR Inspection?

An EICR inspection is a formal assessment of the fixed electrical installation in a property: the consumer unit (fuse box), wiring, sockets, light fittings, switches, earthing and bonding. It checks them against BS 7671, the UK Wiring Regulations.

The report does not “pass” or “fail” a property in the everyday sense. It gives an overall outcome of Satisfactory or Unsatisfactory, together with a coded list of any issues found.

It is not a PAT test, which covers portable appliances, and it does not cover the plug-in items you own. It is about the permanent electrical system built into the building.

Who Needs an EICR Inspection in the UK?

  • Private landlords in England must have the electrical installation inspected and tested at least every five years by a qualified and competent person. They must also give a copy of the report to tenants.
  • Social landlords in England are now covered too. Regulations extending the rules to the social rented sector came into force in November 2025.
  • Scotland and Wales have their own rules for rented property, so check the requirements that apply where your property is.
  • Homeowners have no legal duty, but an EICR is sensible when buying a home, after major works, or if the wiring is old.

Many mortgage lenders, insurers and letting agents also ask for a recent report.

Before the Inspection: Preparation and Planning

A good inspection starts before any test is done. Your electrician will usually:

  1. Agree the scope. This covers how many circuits there are, whether outbuildings or garages are included, and any known problems.
  2. Review earlier paperwork. Previous EICRs, minor works certificates and installation certificates help the electrician understand the system.
  3. Plan the power interruptions. Some tests need the supply off, so we advise tenants or occupants in advance. That is also why people are asked to save work on computers and switch off sensitive equipment.

Step 1: The Visual Inspection

The first stage uses no test instruments at all. The inspector examines the installation by eye, checking for:

  • Damaged, overheated or poorly fitted accessories
  • Cracked or broken sockets and switches
  • Signs of burning, scorching or melting
  • Unsuitable or outdated consumer units, for example units with no RCD protection
  • Poor cable support or DIY wiring that does not meet standards
  • Missing or incorrect labelling
  • Evidence of earthing and bonding to gas and water pipes

A good visual inspection catches many problems before any equipment is connected, and it guides how the rest of the testing is done.

Step 2: Dead Testing Explained

Dead testing means testing circuits with the power switched off and the circuits isolated. This makes it the safest way to check certain characteristics of the wiring.

What is checked during dead testing?

  • Continuity of protective conductors. This confirms the earth connections are unbroken.
  • Continuity of ring final circuits. This confirms sockets on a ring are properly connected and the ring is complete.
  • Insulation resistance. The inspector applies a test voltage to confirm the insulation around the cables is not deteriorating, which could otherwise lead to leakage, shocks or fires.
  • Polarity. This confirms live and neutral conductors are connected to the right terminals, so switches and protective devices sit on the correct side of the circuit.

Why does dead testing matter?

Faults such as damaged insulation or broken earth connections can go unnoticed for years while everything seems to work normally. Dead testing finds them without putting anyone at risk of shock.

It does mean the power will be off, sometimes for an hour or more depending on the property. Planning this with the occupants avoids disruption.

Step 3: Live Testing Explained

Live testing takes place with the power switched on and the installation energised. It measures how the system behaves under real operating conditions, and a competent, trained electrician follows strict safe working practices throughout.

What is checked during live testing?

  • Earth fault loop impedance. This shows how quickly a protective device such as an MCB or fuse would disconnect in the event of a fault. If the value is too high, the device may not trip fast enough to prevent injury or fire.
  • RCD operation. Residual current devices are tested to confirm they trip within the required time, which is vital because they protect against fatal electric shock.
  • Prospective fault current. This measures how much current could flow in a fault, confirming that protective devices are rated to cope.
  • Supply characteristics. The inspector checks the incoming supply and the correct operation of the earthing arrangement.
  • Phase sequence. On three-phase supplies, this confirms the phases are connected in the right order.

Why does live testing matter?

Some safety-critical behaviour can only be observed when the system is powered. A circuit can pass its dead tests and still fail to disconnect quickly enough in a fault. Live testing shows whether the installation protects people as it should.

Step 4: Understanding the Observation Codes

After testing, the electrician records any findings using standard codes:

  • C1 – Danger present. There is a risk of injury and immediate action is needed. The electrician will often make the hazard safe on the day.
  • C2 – Potentially dangerous. Urgent remedial work is required.
  • C3 – Improvement recommended. Not a safety failure, but upgrading is advised.
  • FI – Further investigation required. Something could not be fully assessed and needs more checks.

A report with any C1 or C2 code is classed as Unsatisfactory. In England, landlords generally must arrange remedial work within 28 days (or sooner if the report says so) and provide written confirmation that the work is complete.

Step 5: The Report and What Happens Next

You should receive a clear written report, usually within a few days, covering:

  • The installation’s details and the extent of what was tested
  • A schedule of circuit test results
  • Any observations and their codes
  • The overall outcome (Satisfactory or Unsatisfactory)
  • A recommended date for the next inspection

If remedial work is needed, a reputable inspection company will explain each item in plain English, quote for the repairs and, where appropriate, issue the relevant certificates once work is complete. Keep all of these documents together. Landlords may be asked for them by tenants, local councils, letting agents or insurers.

How Long Does an EICR Inspection Take?

Time depends on the size of the property and the number of circuits, but a typical flat or small house takes a few hours, and larger or more complex properties take longer. Easy access to the consumer unit, switches and sockets makes the process quicker and smoother.

Choosing the Right Provider

Not every electrician is qualified to do an EICR. Choose someone with relevant qualifications in inspection and testing, appropriate insurance, and registration with a recognised competent person scheme. Ask what the inspection covers, how long the report takes, and what happens if remedial work is needed. A provider who explains the process clearly is usually a good sign.

An EICR inspection is more than a box-ticking exercise. By combining a careful visual inspection with dead testing and live testing, an electrician builds a full picture of whether your installation is safe, protecting tenants, occupants and the property itself.

FAQs

1. How often do I need an EICR inspection?

For privately rented homes in England, at least every five years, or sooner if the previous report recommends a shorter interval. Owner-occupiers have no fixed legal requirement, but an inspection every ten years is a common recommendation, and also when you buy a property.

2. What happens if my EICR comes back Unsatisfactory?

An Unsatisfactory result means the inspector found at least one issue coded C1 or C2. Landlords in England generally need to complete the remedial work within 28 days, or sooner if the report requires it, and send written confirmation to the tenant and the local authority if requested.

3. Do I need to be at the property during the inspection?

Not necessarily, as long as the electrician has safe access and the occupants have been told about the power interruptions. Many landlords arrange access through a tenant or letting agent.

4. Is dead testing or live testing more important?

Both are needed. Dead testing checks the condition of the wiring with the power off, while live testing shows whether protective devices such as RCDs react quickly enough in real conditions. An EICR is not complete without both.

5. Who can carry out an EICR inspection?

A qualified and competent person with up-to-date training in inspection and testing under BS 7671, appropriate insurance, and ideally registration with a recognised competent person scheme. Ask to see their credentials before booking.